MS4 - F:MC6H1 PS, changed SCR firing card on Wednesday AP10 – D:QF PS, replaced bad DCCT on Thursday MCenter – F:MC5U and F:MC6H1 were repaired and turned on FMAG load for SpinQuest was successfully tested to 2K Amps. A big thanks to Interlocks group for clearing up the confusing decommissioned safety system cable issue IB1 - Repaired and upgraded PS for magnet service facility new over-current protection and LOTO test points) FAST - Cryomodule (CM) modulator brought back to service Thursday 03/02/23 1500 hours. No evidence of a significant fault was ever discovered. We took an oil sample from the transformer and tested it. The breakdown voltage was 7 kV, which indicates the oil is in bad shape and would need some processing similar to the oil in the gun modulator transformer tank In addition, we will be looking for a quick 30-min downtime of the AP-30 Muon Septum to replace 208V fuses (going from 5 Amp to 4 Amp). I will talk to Gerry Annala about it.